Basic Error - for Reference Reflector
- Error is larger at the beginning and end of the rod or rope electrode. More detailed information can be found in the instruction manual
- MLR-70_-20 in area 0.1 - 0,2 m | 0.2 - 2.0 m | 2.0 - 40 m .....:: ± 5 mm | ± 3 mm | ± 2 mm
- Other Types in area 0.1 - 0.2 m | 0.2 - 2.0 m | 2.0 - 40 m .....:: ± 10 mm | ± 4 mm | ± 2 mm
Maximal Length of Measuring Electrode
- MLR-70_-11 (12): 2 mm
- MLR-70_-32: 12 mm
Dead Zone - for Measuring Sensitivity
- Dead Zone = Blind Zone = Blocking distance
- The length of dead Zone at the beginnig | at the end of the electrode. (The length of dead Zone is 110 mm at the end of rope electrode):::
- Low, Medium, User (1-4): 100 | 0 mm
- High, User (5): 150 | 50 mm
- User (6,7): 200 | 50 mm
- User (8): 250 | 50 mm
Electrical Parameters for Variants Xi (XiT) – Maximum Internal Values
- Uᵢ = 30 Vdc, Iᵢ = 132 mA, Pᵢ = 0.99 W, Cᵢ = 370 nF, Lᵢ = 0.9 mH
Measurement Sensitivity (8 Degrees)
- low (1) - medium (3) - high (5) - user (1 - 8)
Failure Indication (Echo Loss, Internal Failure)
- Adjustable in modes: 3.75 mA, 4 mA, 20 mA, 22 mA, LAST
- Level meter displays last measured value
Internal Resistance | Electric Strength (Electrode - Housing)
Coupling Capacity | Electric Strength (Housing - Supply Leads)
Maximal Current Output Load Resistance for
- U = 24 Vdc, Rmax = 270 Ω | Including 250R resistor in case of HART connection
- U = 22 Vdc, Rmax = 180 Ω
- U = 20 Vdc, Rmax = 90 Ω
Maximum Tensile Strength of the Rope Electrode
Weight (Without Electrode)
- cca 0.5 kg (1 kg variant NT, XiT)