LE3 General-Purpose Transmitter

Brand: Winters Instruments

Specifications
  • Developed for use in general industry and OEM applications, where versatility and economy are requirements 
  • Compact stainless steel construction with ceramic sensor 
  • Available ranges include Inches Hg: -30 up to psi: 0 to 5,000 (kPa: 0 to 34,474, bar: 344.7) 
  • Wide range of mechanical and electrical connections 
  • ±0.5% accuracy 
  • NEMA 4X / IP65 and IP67 
  • CE, CSA and RoHS compliant 
  • Approved for outdoor use 
  • Customizable 

Models matching criteria: 14
  • Pressure Range - psi: 0 to 100
In Stock
Does not ship to VA, United States
  • Pressure Range - psi: 0 to 1,000
In Stock
Does not ship to VA, United States
  • Pressure Range - psi: 0 to 150
In Stock
Does not ship to VA, United States
  • Pressure Range - psi: 0 to 2,000
In Stock
Does not ship to VA, United States
  • Pressure Range - psi: 0 to 60
In Stock
Does not ship to VA, United States
  • Pressure Range - psi: 0 to 200
In Stock
Does not ship to VA, United States
  • Pressure Range - psi: 0 to 300
In Stock
Does not ship to VA, United States
  • Pressure Range - psi: 0 to 3,000
In Stock
Does not ship to VA, United States
  • Pressure Range - psi: 0 to 25
In Stock
Does not ship to VA, United States
  • Pressure Range - psi: 0 to 500
In Stock
Does not ship to VA, United States
  • Pressure Range - Inches Hg: -30
In Stock
Does not ship to VA, United States
  • Pressure Range - psi: 0 to 15
In Stock
Does not ship to VA, United States
  • Pressure Range - psi: 0 to 5,000
In Stock
Does not ship to VA, United States
  • Pressure Range - psi: 0 to 50
In Stock
Does not ship to VA, United States

Specifications

Accuracy

  • ± 0.5 % of Full Scale Output

Approvals & Certifications

  • CE
  • CSA
  • EMC Directive: 2004/108/EC
  • PED: 97/23/EC (Module A), Valid for Devices With, Max.
  • RoHS

BSP Connection

  • G 1/4” Male (DIN 3852)

Burst Pressure

  • psi: 44 to 6,527 (kPa: 303.4 to 45,000, bar: 3.034 to 450)

Cable Material

  • Cable Outlet: PVC

Circuit Protection

  • EMI/RFI Protected: Emission & Immunity According to EN 61326
  • Reverse Polarity Protection
  • Short Circuit Protected

Consumption

  • Current Consumption 2-Wire: 25 mA - Max.
  • Current Consumption 3-Wire Ratiometric: 1.5 mA
  • Current Consumption 3-Wire Voltage: 5 mA (Short-Circuit Current 20 mA)

Diaphragm Material

  • Ceramic AI₂O₃ 96 %

Electrical Connectors

  • 1/2” NPT Female Conduit Fitting
  • DIN 43650-A (ISO 4400)
  • M12 x 1, 4-Pin
  • Micro Connector (Contact Distance 9.4 mm)

Enclosure, Body Material

  • 304 Stainless Steel

Environmental Protection

  • IP65
  • IP66
  • IP67
  • NEMA 4X

Frequency

  • Measuring Rate: 1 kHz

Load

  • 3-Wire: 10 kiloohms Min.

Load Effect

  • 0.05 % of Full Scale Output / kiloohms

Materials of Construction

  • Pressure Port: 304 Stainless Steel

NPT Connection

  • 1/4” NPT Male

Output

  • 2-Wire: 4-20 mA/Vs = 8-32 Vdc
  • 3-Wire Ratiometric: 0.5-4.5 Vs / Vs = 5 ± 0.5 Vdc
  • 3-Wire: 0-10 V/Vs = 14-30 Vdc

Overpressure & Static Pressure Limits

  • Overpressure psi: 15 to 5,802 (kPa: 103.4 to 40,000, bar: 1.034 to 400)

Power Supply Effect

  • 0.05 % of Full Scale Output / 10 V

Pressure Range

  • bar: -1 to 344.7
  • Inches Hg: -30 to 0
  • kPa: -101.4 to 34,474
  • psi: -14.7 to 5,000

Process Temperature

  • -25° to 125° C (-13° to 257° F)

Response Time

  • 2-Wire: < 10 milliseconds
  • 3-Wire: < 3 milliseconds

Seat / Seal Material

  • Seal: FKM
  • Seal: Viton

Sensor, Probe Material

  • Sensor: Ceramic

Shock

  • 500 G, 1 millisecond According to DIN EN 60068-2-27

Stability

  • Long-term Stability: < ± 0.3 % of Full Scale Output/Year at Reference Conditions

Storage Temperature

  • -40° to 85° C (-40° to 185° F)

Temperature Effect

  • < ± 0.5 % of Full Scale Output/10 K

Temperature Range

  • Electronics Environment: -25° to 85° C (-13° to 185° F)

Vibration

  • 10 G at 25 Hz to 2 kHz According to DIN EN 60068-2-6

  • HVAC Systems
  • Hydraulics & Pneumatics Sensing
  • OEM Applications
  • Pump & Compressor Monitoring
  • Refrigeration Systems
  • Suitable for All Process & Automation Control
  • Use in General Industries

show more